MPC Power Station – Supply Air Handling Unit
Design
An internal supply-only unit with a duty of 0.59 m3/s containing the following components:
- G4 and F7 filters with manometer indication
- 20kg/hr resistive steam humidifier
- LPHW heating coil
- EC motor-driven twin fans in a duty-standby arrangement
- Attenuator
The unit achieves a low specific fan power of 0.56 W/l/s, meeting current building regulations.
Controls
The touchscreen controller, supplied loose, includes the following features and functions:
- Supply Fan Manual fan speed control (touch screen adjustable).
- Duty-share & auto-changeover
- Shut-off damper enable
- 0-10V modulating heating demand signal (if required)
- 0-10V modulating humidity demand signal
- Facility for use with remote On/Off signal or PIR sensor
- Volt-free contacts are provided for Common Fault as well as an indication on the touch screen.
- Change the Filter indicator visible via the touch screen.
- Fire alarm interlock facility
- Modbus enabled
Read more about what we can offer
Our bespoke designs cover a wide range of possibilities for AHUs to meet each unique specification.